Surge Protective Device (SPD) Type Application Considerations

2017-04-14

This paper is provided to clarify the use of the different Listed or Recognized Types of
Surge Protective Devices (SPDs) that are used in 50 or 60 Hz power circuits not
exceeding 1000 V as defined in ANSI/UL 1449.
The SPD Types described below are in accordance (paraphrased from) with UL 1449
Third Edition, as follows:
Type 1 SPDs (Listed) Permanently connected, hard-wired SPDs intended for
installation between the secondary of the service transformer and the line side of the main
service equipment overcurrent protective device, as well as the load side of the main
service equipment (i.e. Type 1s can be installed anywhere within the distribution
system). Type 1 SPDs include watt-hour meter socket enclosure type SPDs. Being on the
line side of the service disconnect where there are no overcurrent protective devices to
protect an SPD, Type 1 SPDs must be listed without the use of an external overcurrent
protective device. The Nominal Discharge Current Rating for Type 1 SPDs is either
10kA or 20kA.
Type 2 SPDs (Listed) Permanently connected, hard-wired SPDs intended for
installation on the load side of the main service equipment overcurrent protective device.
These SPDs may also be installed at the main service equipment, but must be installed on
the load side of the main service overcurrent protective device. Type 2 SPDs may or may
not require an overcurrent protection device per their NRTL listing. If a specific
overcurrent protection is required, the SPDs NRTL listing file and labeling/instructions
are required to note the size and type of overcurrent protective device. Note: In some
cases the overcurrent protective device used can impact the nominal discharge rating of
the SPD. For example, the SPD may have a 10 kA nominal discharge current rating
when protected by a 30 Amp circuit breaker and a 20 kA nominal discharge current
rating when protected by a different but specific make and model of overcurrent
protection device. The Nominal Discharge Current Rating for Type 2 SPDs is 3 kA, 5
kA, 10 kA, or 20 kA.
Some key differences between Type 1 and Type 2 SPDs are:
External Overcurrent Protection. Type 2 SPDs may require external overcurrent
protection or it may be included within the SPD. Type 1 SPDs generally include
overcurrent protection within the SPD or other means to satisfy the requirements
of the standard; thus, Type 1 SPDs and Type 2 SPDs that do not require external
overcurrent protection devices eliminate the potential for installing an incorrectly
rated (mismatched) overcurrent protection device with the SPD.
Revision Date 01-31-2013 Page 2 of 3
Nominal Discharge Current Ratings. Available Nominal Discharge Current (In)
ratings of Type 1 SPDs are 10 kA or 20 kA; whereas, Type 2 SPDs may have 3
kA , 5 kA, 10 kA or 20 kA Nominal Discharge Current ratings.
UL 1283 EMI/RFI Filtering. Some UL 1449 Listed SPDs include filter circuits
that have been evaluated as a UL 1283 (Standard for Electromagnetic Interference
Filters) filter. These are complimentary UL Listed as a UL 1283 filter and a UL
1449 SPD. By definition and the scope of UL 1283, UL 1283 Listed filters are
evaluated for load-side applications only, not line-side applications.
Consequently, UL will not complimentary list a Type 1 SPD as a UL 1283 Listed
filter. However, a Type 1 SPD might include a UL 1283 filter as a Recognized
Component within a Listed Type 1 SPD, which has been fully evaluated for lineside
usage. Manufacturers of such products generally offer the identical SPD as a
Type 2 UL 1449 Listed SPD with complimentary Listing as a UL 1283 Listed
filter.
Capacitors. Capacitors utilized in Type 1 SPDs may be evaluated for safety
differently than in Type 2 SPDs. All capacitors in Type 1 SPD applications are
evaluated to UL 810 (Standard for Capacitors). This includes filtering capacitors
referenced above in UL 1283 (Standard for Electromagnetic Interference Filters)
applications. Capacitors in Type 2 SPDs are evaluated to UL 1414 (Standard for
Capacitors and Suppressors for Radio- and Television-Type Appliances) and/or
UL 1283 (Standard for Electromagnetic Interference Filters).
Type 3 SPDs (Listed) These SPDs are called, Point of Utilization SPDs, which are to
be installed at a minimum conductor length of 10 meter (30 feet) from the electrical
service panel unless they are evaluated at Type 2 SPDs (that is, they receive a Nominal
Discharge Current Rating of 3 kA minimum). Typically, these are cord-connected surge
strips, direct plug-in SPDs, or receptacle-type SPDs installed at the utilization equipment
being protected (i.e. computers, copy machines, etc.).
Type 1, 2, 3 Component Assembly SPDs (Component Recognized) These SPDs are
intended to be factory installed into electrical distribution equipment or end-use
equipment. These are Recognized Component SPDs evaluated for use in Type 1, 2 or 3
SPD applications. Such component SPDs must pass all the same electrical safety failure
tests as listed Type 1, 2 or 3 SPDs. While these SPDs are 100% compliant from a safety
failure testing point of view, these Type 1, 2 and 3 component assembly SPDs have
conditions of acceptability such as exposed terminals or other mechanical construction
that requires them to be installed or housed within a listed assembly to provide protection
from exposure to live parts or other requirements. These Type 1, 2 or 3 Recognized
Component SPDs should not be confused with ANSI/UL 1449-2006 Type 4 Component
Assemblies and Type 5 discrete SPD components that require additional components
(possibly safety disconnectors), design and testing in order to be used as a complete surge
protective device.
Revision Date 01-31-2013 Page 3 of 3
Type 4 Component Assembly SPD (Component Recognized) –– These component
assemblies consist of one or more Type 5 SPD components together with a disconnector
(integral or external) or a means of complying with the limited current tests in UL 1449,
Section 39.4. These are incomplete SPD assemblies, which typically are installed in
listed end-use products as long as all conditions of acceptability are met. These Type 4
component assemblies are incomplete as an SPD, require further evaluation and are not
permitted to be installed in the field as a stand-alone SPD. Often, these devices require
additional overcurrent protection.
Type 5 SPD (Component Recognized) Discrete component surge protection devices,
such as MOVs that may be mounted on a printed wiring board, connected by its leads or
provided within an enclosure with mounting means and wiring terminations. These Type
5 SPD components are incomplete as an SPD, require further evaluation and are not
permitted to be installed in the field as a stand-alone SPD. Type 5 SPDs are generally the
components used in the design and construction of complete SPDs or other SPD
assemblies

Last one: UL 1449 4th Edition Announced Next one: Not more.

Home   |   About Us  |   Products  |   Technology  |   Solutions  |   Agent  |   News  |   Recruitment  |   Contact Us

Tel: 0086-771-2865199

No.1205, A2 South, Industrial Investment Jiangnan Enterprise Park, Xiajin Road No.12, Jiangnan District, Nanning City,Guangxi Province,China

Copyright Guangxi NQT Electronic Technology Co.,Ltd 桂ICP备09008744号-1 Technical support: Resonance

Guangxi NQT Electronic Technology Co.,Ltd Copyright 桂ICP备09008744号-1 Tel:0086-771-2865199 Address:No.1205, A2 South, Industrial Investment Jiangnan Enterprise Park, Xiajin Road No.12, Jiangnan District, Nanning City,Guangxi Province,China Technical support: Resonance