UL 1449 4th Edition Announced
Location: Home > Technology > Technology Support

Technology

  • Research and Development
  • Quality System
  • Technology Support
  • Laboratory

UL 1449 4th Edition Announced

2017-04-14

Effective March 2016, Underwriters Laboratories Inc. (UL) has announced the release of UL 1449 4th edition covering low voltage AC power surge protection devices. The latest refinements of the testing and product marking allow DEHN’s Type 1 Component Assemblies to fit the larger market needs for lightning current SPDs.

The SPD types as defined by UL:

SPD Type        Coverage
Type 1
  • Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of service equipment.
  • Installed without the use of external overcurrent protective device
Type 2
  • Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device
Type 3
  • Point-of-utilization SPDs

  • Installed at a minimum conductor length of 10 metres (30 feet) from the electrical service panel

Type 4
  • Component assembly consisting of one or more Type 5 components (typically MOV or SASD)

  • Must comply limited current tests and In

  • Not tested as standalone devices to intermediate and high current faults

Type 5
  • Discrete component surge suppressors such as surge components (MOV or SASD)

  • May be mounted on a PCB connected by leads

  • Can be utilized within an enclosure with mounting means and wiring terminations

  • Not tested to low, intermediate or high fault currents

  • Must be mounter within another enclosure

 

Testing Requirements for type 4 and 5 SPDs:

Test Criteria

Type 4 SPD

Type 5 SPD

I Leakage (initial)

Required

Required

Dielectric Voltage Withstand

Required

Required

Vn (Before and After IN)

Required

Required

Measured Limiting Voltage (MLV)

Required

Required

Disconnector

Required

Not Applicable

Limited Current

Required

Not Applicable

Grounding Continuity

Optional

Optional

Fault and Overcurrent

Optional

Optional

Insulation Resistance

Optional

Optional

 

 

The marking includes:

  • Manufacturer Name
  • Catalog Number
  • SPD Type
  • Electrical ratings
  • Nominal discharge current (In) Rating
  • Maximum continuous operating voltage rating (MCOV)
  • Voltage protection rating (VPR)
  • Measured limiting voltage (MLV)
  • Date or period of manufacture
  • Short circuit current rating (SSCR)

Home   |   About Us  |   Products  |   Technology  |   Solutions  |   Agent  |   News  |   Recruitment  |   Contact Us

Tel: 0086-771-2865199

No.1205, A2 South, Industrial Investment Jiangnan Enterprise Park, Xiajin Road No.12, Jiangnan District, Nanning City,Guangxi Province,China

Copyright Guangxi NQT Electronic Technology Co.,Ltd 桂ICP备09008744号-1 Technical support: Resonance

Guangxi NQT Electronic Technology Co.,Ltd Copyright 桂ICP备09008744号-1 Tel:0086-771-2865199 Address:No.1205, A2 South, Industrial Investment Jiangnan Enterprise Park, Xiajin Road No.12, Jiangnan District, Nanning City,Guangxi Province,China Technical support: Resonance